Basic Info
  • Model NO.: VS1
  • Operation: Electric Type
  • Arc-extinguishing Medium: Vacuum
  • Structure: Vcb
  • Type: Circuit Breaker
  • Certification: CB
  • Transport Package: Wooden Package
  • Origin: China
  • Breaking Capacity: High Voltage Circuit Breakers
  • Speed: Normal Type Circuit Breaker
  • Installation: Insert
  • Poles Number: 3
  • Function: Vacuum Circuit Breaker
  • Trademark: CNHK
  • Specification: 0.036
  • HS Code: 8535210000
Product Description

Introduction : 

 

VS1 -12KV fixed type indoor vacuum circuit breaker is rated voltage 12kV, three-phase AC 50Hz/60Hz Indoor high-voltage switchgear ,applied for power stations, substations, and industrial and mining enterprises to control or  protection transmission and distribution systems , specially for the important high altitude breaking load and frequent operation place.

  

Circuit breaker manufacturing accordance with our national standard GB1984-2003 <AC high voltage circuit breakers>, DL / T403-2000<3.6 ~ 40.5kV Indoor Vacuum Circuit Breaker ordering technology>; and the related IEC standards And reliable interlock function.

  

Circuit breaker operating mechanism for the spring energy storage type, can use AC and DC energy storage operations, can also be used manually.

 

Circuit breaker can also be equipped with long life permanent magnetic actuator, mechanical life can reached 60000 times , can be used for extremely Frequent operation place,

 

Circuit breaker designed to repackage the structure before and after, both can be used as a fixed installation unit, Can also be equipped with the chassis as used in the mounted unit.

  

The use of environmental conditions:

 

1.Ambient temperature: not higher than +40 °C, not less than -15°C   

2. Altitude: not exceed 1000m. 

3. Relative humidity: daily average of not more than 95%, month average of not more than 90%. 

4. Earthquake intensity: not more than ten. 

5. No fire, explosion hazard, serious filthy, chemical corrosion, as well as places of intense vibration.

  

Mainly technical parameters
NOItemUnitsparameters
1Rated voltageKV12
2Rated FrequencyHZ50/60
3Rated CurrentA4000A 
4Rated short-circuit breaking currentKA40KA
5Rated short-circuit closing current (peak)KA50 63 80
6Rated short-circuit durationS4
7Rated short-circuit breaking current breaking number nos50s
8Rated operating sequence 0-0.3s-CO-180s-CO
9Rated lightning impulse withstand voltagekv125
101min power frequency withstand voltageKV65
11Closing timems≤ 70
12opening timems≤ 50
13Mechanical lifeTimes20000
14Rated Storage and operation voltageVAC DC 220/110
15Breaking lifems≤ 80
16Storage lifes≤ 10
       Adjust the parameters of mechanical properties:
NoItemUnitParameters
1Contact distancemm14±1
2   Contact Over-travelmm3.5±1
3Closing speedm/s1.0±0.2
4Opening speedm/s1.3±0.2
5Contact closing spring timems≤2
6Rated contact pressureN 40KA (4000±200) 
7Three phase closing opening asynchronyms≤2

Vs1 Hv Vacuum Circuit Breaker
Vs1 Hv Vacuum Circuit Breaker
Vs1 Hv Vacuum Circuit Breaker
Vs1 Hv Vacuum Circuit Breaker
Vs1 Hv Vacuum Circuit Breaker
Vs1 Hv Vacuum Circuit Breaker
 
Send your message to this supplier
Avatar
Miss Amber
sales manager
*From:
To: Miss Amber
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

Find Similar Products By Category