Model NO.
KYN28-12
Voltage Level
Medium Voltage
Installation
Removable
Structure
Withdrawable
Current
AC
Circuit Breaker
with Trollery
Screen
LED
Voltage
12kv 24kv
Requirement
Single Line Diagram
Transport Package
Wooden
Specification
1000*2300*800
Trademark
CNHK
Origin
China
HS Code
8537209000
Production Capacity
500PCS Per Month

Product Description

KYN28A-12(Z) Metalclad AC Indoor Enclosed Switchgear,
Withdrawable type
 
 
1. General Description
1.1 Application: In the power system of 3.6 V, for control, protection and monitoring.VCBs produced
By CNHK or VCBs produced by other manufactures could be installed in the switchgear panel.
1.2 Standards : IEC 62271-200
1.3 Parameters: Rated voltage: 3.6 V
1.4 Rated current: 630-5000A
1.5 Rated short-circuit breaking current: 16 kA
 
2.Features:
2.1.Compact design
2.2.Easy operation and installation
2.3.Reliable interlock
2.4.Less Maintenance

3.Technical Data
No.ItemUnitData
3.1Rated voltagekV3.6,7.2,12
3.2Rated current of circuit breakerA630,1250,1600,2000,2500,3150,4000,5000
Rated current of switchgearA630,1250,1600,2000,2500,3150,4000,5000
3.3Rated frequencyHz50
3.4
 
Rated short-circuit breaking currentkA16,20,25,31.5,40,50
Rated short-time withstand currentkA16,20,25,31.5,40,50
Rated short circuit continuous time s4
3.5Rated peak withstand currentkA40,50,63,80,100,125
Rated short-circuit closing current(peak)kA40,50,63,80,100,125
3.6Rated insulation level: 1min power frequency withstand voltagekV24,32,42 between poles, pole to earth
kV24,32,48 between open contacts
3.7Rated insulation level: Lighting impulse withstand voltage(peak)kV40,60,75 between poles, pole to earth
kV46,70,85 between open contacts
3.8Rated power frequency withstand voltage kV95/1min
3.9Protection levelSwitchgear shell  IP3X
Compartments(door opened) IP2X when the CPT and CB doors are open.
Note: 1.The short circuit capacity of the current transformer should be separately considered.
       2. See technical parameters of ZN63A(VS1)-12 in related product of our company.












 