Item | Unit | Data | ||||
Rated voltage | kV | 40.5 | ||||
Rated insulation level | 1min power frequency with stand voltage | Dry test | kV | 95 | ||
Wet test | kV | 80 | ||||
Rated lightning impulse withstand voltage | kV | 185 | ||||
Rated frequency | Hz | 50 | ||||
Rated current | A | 1250 | 1600 | 2000 | ||
Rated short-circuit breaking current | kA | 20 | 25 | 31.5 | ||
Rated short-circuit making current(peak) | 50 | 63 | 80 | |||
Rated short-time withstand current | kA | 20 | 25 | 31.5 | ||
Rated peak withstand current | 50 | 63 | 80 | |||
Rated duration of short-circuit | s | 4 | 4 | 4 | ||
Rated operation sequence | O-0.3s-CO-180S-CO* | |||||
Mechanical life(grade M2) | times | 10000 | ||||
Electrical life | E2 class | |||||
Overall breaking time | s | |||||
Rated breaking current of cables charging | A | 50 | ||||
Rated breaking times of short-circuit breaking current | times | 20 | ||||
Peak value of TRV | kV | 114 | ||||
Rated operating voltage and auxiliary circuit voltage | V | DC220,110,24 AC220,110,24 | ||||
Weight | kg | 800 |