Item | Index | ||
Voltage | AC range | Basic range: 25V,100V,250V,600V | |
automatic range: 15V~600V | |||
DC range | Basic 100mV,25V,100V,250V,600V | ||
automatic range: 15V~600V | |||
Regulation range | 0~130% UN | ||
Regulation fineness | 0.002%UN | ||
Maximum output capacity | ≥20VA/Phase | ||
Fineness | 0.05 (100mV: 0.1) | ||
Current | AC range | Basic range: 0.1A,1A,5A,25A | |
automatic range: 0.05A~25A | |||
DC range | Basic range: 20µA,200µA,2mA,20mA,0.1A,1A,5A,25A | ||
automatic range: 20µA~20mA & 0.1A~25A | |||
Regulation range | 0~130%IN(25A: 0~120%) | ||
Regulation fineness | 0.002%IN | ||
Maximum output capacity | ≥20VA/Phase | ||
Accuracy | 0.05 | ||
Frequency | Regulation range | 40HZ~70HZ | |
Regulation fineness | 0.01HZ | ||
Regulation accuracy | ±0.01HZ | ||
Phase | Regulation range | 0~359.99° | |
Regulation fineness | 0.01° | ||
Accuracy | ±0.2°( rated output voltage current at full range) | ||
Three phase power accuracy | 0.05(reactive power: 0.1) | ||
Three phase voltage symmetry | Three phase four line 120°±0.2°, Three phase three line 60°±0.2° | ||
Voltage current waveform distortion | < 0.3% | ||
Harmonic component | 2~31th order(when >11, only odd numbers can be set) | ||
Voltage current power stability | ≤0.01%(1min) | ||
Accuracy | 0.02(0~±20mA,0~±5V) | ||
Integrated error | 0.05%(energy meter 0.1%) | ||
Weight | 18kg | ||
Dimension | 432×428×175mm | ||
Power supply | 220V±10% |