Power Box Good Quality Made in Huanghua Group

Product Details
Customization: Available
Certification: CCC, ISO9001
Shell Material: Hot-DIP Al-Zn Alloy-Coated Steel Sheet
Manufacturer/Factory & Trading Company

360° Virtual Tour

Industry-leading Audited Factory

Diamond Member Since 2017

Suppliers with verified business licenses

Audited Supplier Audited Supplier

Audited by an independent third-party inspection agency

to see all verified strength labels (30)
Find Similar Products

Basic Info.

Model NO.
mns
Voltage Level
Medium Voltage
Installation
Removable
Structure
Withdrawable
Current
AC
Circuit Breaker
with Trollery
Screen
LED
Voltage
12kv 24kv
Requirement
Single Line Diagram
Transport Package
Wooden
Specification
1000*2300*800
Trademark
CNHK
Origin
China
HS Code
8537209000
Production Capacity
500PCS Per Month

Product Description

KYN28A-12(Z) Metalclad AC Indoor Enclosed Switchgear,
Withdrawable type
 
 
1. General Description
1.1 Application: In the power system of 3.6 V, for control, protection and monitoring.VCBs produced
By CNHK or VCBs produced by other manufactures could be installed in the switchgear panel.
1.2 Standards : IEC 62271-200
1.3 Parameters: Rated voltage: 3.6 V
1.4 Rated current: 630-5000A
1.5 Rated short-circuit breaking current: 16 kA
 
2.Features:
2.1.Compact design
2.2.Easy operation and installation
2.3.Reliable interlock
2.4.Less Maintenance

3.Technical Data
No.ItemUnitData
3.1Rated voltagekV3.6,7.2,12
3.2Rated current of circuit breakerA630,1250,1600,2000,2500,3150,4000,5000
Rated current of switchgearA630,1250,1600,2000,2500,3150,4000,5000
3.3Rated frequencyHz50
3.4
 
Rated short-circuit breaking currentkA16,20,25,31.5,40,50
Rated short-time withstand currentkA16,20,25,31.5,40,50
Rated short circuit continuous time s4
3.5Rated peak withstand currentkA40,50,63,80,100,125
Rated short-circuit closing current(peak)kA40,50,63,80,100,125
3.6Rated insulation level: 1min power frequency withstand voltagekV24,32,42 between poles, pole to earth
kV24,32,48 between open contacts
3.7Rated insulation level: Lighting impulse withstand voltage(peak)kV40,60,75 between poles, pole to earth
kV46,70,85 between open contacts
3.8Rated power frequency withstand voltage kV95/1min
3.9Protection levelSwitchgear shell  IP3X
Compartments(door opened) IP2X when the CPT and CB doors are open.
Note: 1.The short circuit capacity of the current transformer should be separately considered.
       2. See technical parameters of ZN63A(VS1)-12 in related product of our company.

















 