ZN85-40.5 ( 40.5kV) Vacuum Circuit Breaker, Indoor Type
General
1.1Ratings: Rated voltage 40.5kV, Rated current up to 2000A, AC50HZ
1.2 Application: for the control and protection of substation and equipments; making and breaking short-circuit current under various operating status of electric network.
1.3 Standard: IEC62271-100
2. Type and Interpretation:
Z N 85 -40.5 / T -
T: Operating mechanism code: Spring operating mechanism;
40.5: Rated voltage(kA)
85: Design code
N: Indoor
Z: Vacuum circuit breaker
3. Working Condition
3.1 Ambient air temperature: -15ºC~ +40ºC
3.2 Altitude: ≤1000m
3.3 No operating in such places as subject to dust, smog, corrosive/flammable gas, vapor and salt pollution.
3.4 Relative humidity: Daily average 95%
Monthly average 90%
3.5 Water vapor pressure: Daily average
Monthly average 1.8kPa
3.6 The external shocking and earthquake could be neglected.
3.7 The amplitude of electromagnetic interference in the secondary system 1.6kV
Note: 1.Customized products are available on your requirements.
4. Main Technical Parameter
Item | Unit | Data |
Rated voltage | kV | 40.5 |
Rated current | A | 630 ,1250,1600,2000 |
Rated frequency | Hz | 50 |
Rated insulation level | 1min power frequency withstand voltage(Vacuum open contacts) | kV | 95 between poles, to earth/110(virtual value) |
Rated lightning impulse withstand voltage(Vacuum open contacts) | 185 between poles, to earth/215(Peak value) |
Rated short-time withstand current | | 20,25, 31.5 |
Rated withstand current (peak) | | 50,63,80 |
Breaking time | mS | 80 |
Rated short-circuit breaking current | kA | 20,25, 31.5 |
Rated short-circuit making current(peak) | 50,63,80 |
Rated duration time of short-circuit | S | 4 |
Rated operating sequence | | O+t-CO-t'-CO*, O+0.3s-CO-180s-CO |
Mechanical life(grade M2) | times | M2 Class (10000times) |
Breaking times of rated short-circuit making current | times | 20 |
Rated unit capacitor bank breaking current | A | 630 |
Rated back to back capacitor bank breaking current | 400 |
Rated operating voltage | V | -110/ 110, -220/ 220 |
5. Overall and Installation Dimension
5.1 Overall and installation dimension of fixed type circuit breaker
parameters
Total length(mm) | Distance of poles L1(mm) |
1689 | 400 |
1788 | 472 |
6.Ordering Information
Please indicate the following items when order:
6.1 Type, name and quantity
6.2 Rated voltage , rated current and rated short-circuit breaking current.
6.3 Rated voltage of auxiliary circuit
6.4 Name and quantity of spare parts.
Note: Customized products are available per your requirements.